EHON non-segregated three-phase busducts (NSPB busducts)
Non-segregated three-phase circular busducts are a more economical and more reliable solution for current connections than three-phase rectangular busducts type and cables.
They are highly reliable and maintenance-free. These advantages are achieved by a special welding technology of the conductors and enclosure at the stage of the busduct assembly. This avoids bolted connections on the entire length of the busduct. This way a busduct may be made up to the IP65 degree of protection.
HOLDUCT provides three-phase busducts optimized for the needs of the customer in order to get the most savings through:
- reduction of losses,
- reduction of assembly time,
- busduct trunking and support structure configuration.
Our support engineers are ready to help you even at the stage of the development of a power plant concept project.
Summary of the characteristics of round and rectangular busducts | |
Rectangular busduct | Round busduct |
Bolted connections of current conductors and enclosure. Problem:
|
Welded joints of current conductors and enclosure Solution:
|
Parallel arrangement of current conductors. Problem:
|
Symmetrical localisation of current conductors in the housing every 120°. Solution:
|
Degree of protection IP65 Problem:
|
Degree of protection IP65 Solution:
|
Short sections for transport (approx. 4m) due to lower mechanical strength. Problem:
|
Transport sections up to 12m long. Solution:
|
Design:
A three-phase circular busduct is a shielded, self-supporting, naturally cooled air-insulated busduct.
Three phase conductors are arranged symmetrically in a common housing and supported on supporting insulators.
This design reduces the impact of short-circuit currents on the busduct system and minimizes the emission of electromagnetic fields.
Fitting the busduct with a dry-air overpressure system ensures its safe operation in the harshest environments, eliminating the danger of humid and polluted air entering into the busduct.
The busduct may be made with maintenance hatches or without them. The use of maintenance hatches allows for monitoring the condition of insulators and their possible replacement.
Individually designed supporting structures allow 12-30 metre spacing between them.
Delivery includes:
- busduct,
- tap-off busducts to auxiliary transformers, chokes,
- connections to equipment (generator, transformers, generator circuit breaker, cabinets),
- supporting structures,
- transformer, lightning arrester and capacitor cabinets,
- dry-air overpressure system,
- High-voltage disconnectors.
Electrical parameters:
- Conductor material: aluminium or copper,
- Enclosure material: aluminium,
- Nominal current: up to 7kA,
- Nominal voltage: up to 36kV,
- Short-circuit current: up to 250kA
- Conformity to standards: ANSI, IEC.
- Degree of protection: IP65.
Applications:
- Main Generator Leads busducts for currents up to 7kA and voltage up to 36kV,
- power distribution systems for industry and power engineering,
- oil refinery and chemical plants,
- Thermal power plants and heat plants,
- hydroelectric power plants,
- waste-to-energy power plants.